Industrial Modular UPS — Full Specifications
XGW HM / HMH / HML modular UPS families. Parameters apply across the modular platform; frame-specific values are noted where they differ. Source: XGW Back-up UPS Catalog 2026.
Model Families
| Family | Voltage (L-L) | Power range | Typical application |
|---|---|---|---|
| HM Series | 380/400/415 V | 15 – 600 kVA | General data centre & industrial on global 400 V grids |
| HM (large frame) | 380/400/415 V | 50–600 / 62.5–500 kVA | Mega data centres, up to 1.8–2.0 MVA in parallel |
| HMH Series | 480 V | 60 – 720 kVA | North-American 480 V installations |
| HML Series | 200/208/220 V | 12 – 360 kVA | 208 V systems, edge IT, medical, light industrial |
Electrical — Input
| Connection | 3P5W (3P+N+PE) |
|---|---|
| Rated voltage | HM 380/400/415 V · HMH 480 V · HML 200/208/220 V (L-L); 220/230/240 V (L-N) for HM |
| Rated frequency | 50 / 60 Hz |
| Input power factor | > 0.99 |
| Current distortion (THDi) | < 3% at 100% linear load |
| Input voltage range | HM 304–478 V full load (228 V derate 100%→75%) HMH 384–528 V full load (288–384 V derate) HML 166–261 V full load (125–166 V derate) |
| Frequency range | 40 – 70 Hz |
Electrical — Output
| Topology | Online double conversion, 3P/3P (selected frames 3P/1P, 1P/1P) |
|---|---|
| Rated voltage | HM 380/400/415 V · HMH 480 V · HML 200/208/220 V (L-L) |
| Rated frequency | 50 / 60 Hz |
| Output power factor | 1.0 (unity) |
| Voltage accuracy | ± 1.0% |
| Load regulation | < 5% (20% → 80% → 20% step load) |
| Recovery time | < 20 ms (0% → 100% → 0% step load) |
| Output THDu | < 1% linear · < 5% non-linear (IEC 62040-3) |
| Crest factor | 3 : 1 |
| Phase accuracy | 120° ± 0.5° |
| Overload — inverter | 110% 1 h · 125% 10 min · 150% 1 min · >150% 200 ms |
| Overload — bypass | 110% continuous · 110–125% 5 min · 125–150% 1 min · >150% 1 s |
Battery & Synchronisation
| Battery voltage | HM / HMH ±240 VDC · HML ±120 VDC |
|---|---|
| Charging capacity | 20% × Pout |
| Charging accuracy | ± 1% |
| Sync window | ±0.5 – ±5 Hz (default ±3 Hz) |
| Slew rate | 0.5 – 3 Hz/s (default 0.5 Hz/s) |
| Transfer / response | 0 ms (online double conversion, no break) |
Control, Communication & Mechanical
| Display | LED + 7″ / 10″ touch LCD with IoT functions; intelligent self-diagnosis, fault recording, large history storage |
|---|---|
| Communication (std) | USB, RS232, RS485, dry contact, cold start, air filter |
| Options | SNMP card, AS400 card, parallel kit, SPD, LBS (load bus sync) |
| Protection class | IP20 |
| Power module (W×D×H) | 442×659×174 mm (large frames) · 440×678×85 mm 2U (30 kW) · 440×555×85 mm 2U (20 kW) |
| Cabinet (W×D×H) | 600×1000×1600 / 600×1000×2000 / 1200×1100×2000 mm (HM/HMH) · 482×700/816 mm rack (HML) |
Environment & Certification
| Operating temperature | 0 – 40 °C |
|---|---|
| Storage temperature | -25 – 70 °C |
| Humidity | 0 – 95% RH, non-condensing |
| Noise (1 m) | 65 dB @ 100% load (small frames) · 72 dB @ 100% load (large frames); 62 / 69 dB @ 45% load |
| Safety | IEC 62040-1, IEC 60950-1 |
| EMC / EMS | IEC 62040-2, IEC 61000-4-2 (ESD), -4-3 (RS), -4-4 (EFT), -4-5 (Surge) |
| Efficiency | HM / HMH up to 96% · HML ≥93% (normal & battery mode) |
Frequently Asked Questions
Concise, citable answers for specifiers and AI search.
Modular vs monolithic UPS?
Modular scales incrementally with load and allows hot-swap modules; monolithic suits fixed, large standalone loads.
How do I size backup runtime?
Base it on critical load in kW and target minutes; external battery cabinets extend runtime well beyond the built-in bank.